Deep-cycle gel.
Tough on heat and cycling.
A 12 V 192 Ah gel VRLA battery for solar, deep-cycle, mobility and marine use. The gelled electrolyte gives strong deep-cycle life and tolerance to heat and irregular charging. Sealed, maintenance-free and non-spillable, with LT-M8 terminals.

Sealed gel VRLA
Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.
LT-M8 terminals
LT-M8 terminals for secure bolted cable connections.
Gelled electrolyte
Fumed-silica gel immobilises the electrolyte for deep-cycle life and heat tolerance.
Standard footprint
382 × 180 × 375.5 mm case.
MECHANICAL
| Length | 382 mm ±2.5 |
| Width | 180 mm ±1.5 |
| Container height | 351 mm ±2.5 |
| Overall height | 375.5 mm ±2.5 |
| Approx. weight | 63.5 kg ±3% |
| Container material | ABS, UL94-HB (UL94-V0 optional) |
| Terminal type | LT-M8 terminal |
ELECTRICAL
| Nominal voltage | 12 V |
| Chemistry | GEL VRLA (sealed) |
| Capacity, 20 hr (C20) | 192 Ah |
| Capacity, 10 hr (C10) | 180 Ah |
| Capacity, 5 hr (C5) | 155 Ah |
| Rating basis | to 1.80 V/cell @ 25°C |
| Float voltage @ 25°C | 13.5 – 13.8 V |
| Equalizing voltage @ 25°C | 14.4 – 15.0 V |
| Max charge current | 54 A |
| Max discharge current | 1080 A (5 s) |
| Internal resistance (charged) | ≈ 6.0 mΩ |
| Operating temp. (dis / chg) | −15°C~50°C / −15°C~40°C |
| Storage temp. | −15°C~40°C |

ATB-GEL-DCG12-200T — technical data
| F.V (V/cell) / Time | 30 min | 45 min | 1 h | 3 h | 5 h | 8 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 181 | 136 | 114 | 50.0 | 33.6 | 22.8 | 19.0 | 10.2 |
| 1.67 V | 170 | 130 | 110 | 49.6 | 33.4 | 22.6 | 18.9 | 10.2 |
| 1.70 V | 166 | 127 | 108 | 49.0 | 32.8 | 22.4 | 18.7 | 10.1 |
| 1.75 V | 158 | 123 | 105 | 47.4 | 31.8 | 22.0 | 18.5 | 9.80 |
| 1.80 V | 151 | 118 | 93.5 | 45.6 | 31.0 | 21.8 | 18.0 | 9.59 |
| 1.85 V | 130 | 104 | 84.5 | 41.6 | 29.4 | 20.8 | 17.6 | 9.11 |
| F.V (V/cell) / Time | 30 min | 45 min | 1 h | 3 h | 5 h | 8 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 324 | 248 | 214 | 95.3 | 65.1 | 44.4 | 37.2 | 19.6 |
| 1.67 V | 310 | 239 | 209 | 94.9 | 64.7 | 44.2 | 37.0 | 19.4 |
| 1.70 V | 303 | 236 | 205 | 93.7 | 63.9 | 44.0 | 36.8 | 19.2 |
| 1.75 V | 293 | 229 | 201 | 92.1 | 62.3 | 43.4 | 36.6 | 18.8 |
| 1.80 V | 283 | 222 | 181 | 88.9 | 60.5 | 42.8 | 35.6 | 18.2 |
| 1.85 V | 246 | 197 | 164 | 81.3 | 57.7 | 41.2 | 35.0 | 17.5 |
EFFECT OF TEMPERATURE ON CAPACITY (10 HR)
| Temperature | Capacity (10 HR) |
|---|---|
| 40 °C | 102% |
| 25 °C | 100% |
| 0 °C | 85% |
| −15 °C | 65% |
SELF-DISCHARGE CHARACTERISTICS
| Storage time | Remaining capacity |
|---|---|
| 3 months | 91% |
| 6 months | 82% |
| 12 months | 64% |
Discharge Characteristics

Charging Characteristics

Capacity Retention (Self-Discharge)

Float Service Life

STANDARDS & QUALITY
Gel VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.
Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the gel VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.