Lead-carbon AGM.
Built for partial state of charge.
A 12 V 245 Ah lead-carbon AGM VRLA battery. A carbon additive in the negative active material suppresses sulfation under partial state of charge, giving higher cycle life and faster charge acceptance. Sealed, maintenance-free and non-spillable, with M8 bolt terminals.

Sealed AGM VRLA
Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.
M8 bolt terminals
Threaded M8 terminals for secure bolted cable connections in UPS, telecom and storage systems.
Carbon-enhanced plates
Carbon in the negative plate resists sulfation in partial-state-of-charge use.
Standard footprint
520 × 268 × 225 mm case.
MECHANICAL
| Length | 520 mm ±2.5 |
| Width | 268 mm ±2.0 |
| Container height | 220 mm ±2.5 |
| Overall height | 225 mm ±2.5 |
| Approx. weight | 72 kg ±3% |
| Container material | ABS, UL94-HB (UL94-V0 optional) |
| Terminal type | M8 bolt terminal |
ELECTRICAL
| Nominal voltage | 12 V |
| Chemistry | AGM VRLA (sealed) |
| Capacity, 20 hr (C20) | 245 Ah |
| Capacity, 10 hr (C10) | 230 Ah |
| Capacity, 5 hr (C5) | 208.3 Ah |
| Rating basis | to 1.80 V/cell @ 25°C |
| Float voltage @ 25°C | 13.5 – 13.8 V |
| Equalizing voltage @ 25°C | 14.4 – 15.0 V |
| Max charge current | 75 A |
| Max discharge current | 1500 A (5 s) |
| Internal resistance (charged) | ≈ 3.0 mΩ |
| Operating temp. (dis / chg) | −15°C~50°C / −15°C~40°C |
| Storage temp. | −15°C~40°C |

ATB-AGM-LC12-230 — technical data
| F.V (V/cell) / Time | 30 min | 45 min | 1 h | 3 h | 5 h | 8 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 245 | 177 | 148 | 64.8 | 44.7 | 28.8 | 23.9 | 12.8 |
| 1.67 V | 242 | 175 | 146 | 64.4 | 44.0 | 28.3 | 23.7 | 12.6 |
| 1.70 V | 239 | 172 | 145 | 63.6 | 43.1 | 27.9 | 23.5 | 12.4 |
| 1.75 V | 234 | 169 | 142 | 62.5 | 42.3 | 27.4 | 23.3 | 12.3 |
| 1.80 V | 229 | 163 | 135 | 61.3 | 41.7 | 27.4 | 23.0 | 12.2 |
| 1.85 V | 210 | 154 | 130 | 56.5 | 39.8 | 26.0 | 21.5 | 11.8 |
| F.V (V/cell) / Time | 30 min | 45 min | 1 h | 3 h | 5 h | 8 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 450 | 329 | 280 | 124 | 86.4 | 56.4 | 46.5 | 25.2 |
| 1.67 V | 448 | 327 | 278 | 124 | 85.4 | 55.7 | 46.0 | 25.0 |
| 1.70 V | 444 | 324 | 275 | 123 | 84.0 | 55.0 | 45.5 | 24.7 |
| 1.75 V | 439 | 321 | 271 | 121 | 83.0 | 54.3 | 45.1 | 24.5 |
| 1.80 V | 434 | 311 | 260 | 119 | 81.8 | 54.1 | 44.9 | 24.2 |
| 1.85 V | 401 | 296 | 252 | 110 | 78.0 | 51.5 | 42.8 | 23.5 |
EFFECT OF TEMPERATURE ON CAPACITY (10 HR)
| Temperature | Capacity (10 HR) |
|---|---|
| 40 °C | 102% |
| 25 °C | 100% |
| 0 °C | 85% |
| −15 °C | 65% |
SELF-DISCHARGE CHARACTERISTICS
| Storage time | Remaining capacity |
|---|---|
| 3 months | 91% |
| 6 months | 82% |
| 12 months | 64% |
Discharge Characteristics

Charging Characteristics

Capacity Retention (Self-Discharge)

Float Service Life

STANDARDS & QUALITY
AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.
Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.