AGM  /  HR Series  /  Datasheet

ATB AGM HR12-92

HR Series · High-Rate AGM VRLA
ATB-AGM-HR12-92

High-rate AGM.
Power for UPS bursts.

A 12 V 22 Ah high-rate AGM VRLA battery for short-duration, high-current UPS discharge. Sealed, maintenance-free and non-spillable, with M5 bolt terminals.

ATB-AGM-HR12-92
12 V
Nominal voltage
92 W
Per cell · 15 min to 1.67 V
330 A
Max discharge (5 s)
6.30 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

M5 bolt terminals

Threaded M5 terminals for secure bolted cable connections in UPS and standby systems.

High-rate discharge

Optimised for short, high-current discharge in UPS systems.

Standard footprint

181 × 77 × 167 mm case.

SPECIFICATIONS

MECHANICAL

Length181 mm ±1.5
Width77 mm ±1.0
Container height167 mm ±1.5
Overall height167 mm ±1.5
Approx. weight6.30 kg ±5%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeM5 bolt terminal

ELECTRICAL

Nominal voltage12 V
ChemistryAGM VRLA (sealed)
Nominal capacity92 W/cell (15 min to 1.67 V/cell, 25°C) · 22 Ah (C20) · 14.4 Ah (C1)
Float voltage @ 25°C13.5 – 13.8 V
Equalizing voltage @ 25°C14.4 – 15.0 V
Max charge current6.60 A
Max discharge current330.00 A (5 s)
Internal resistance (charged)≈ 9.5 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-HR12-92 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time5 min8 min10 min15 min20 min30 min60 min1.5H
1.60 V94.572.465.449.239.026.915.311.6
1.67 V91.570.362.647.638.026.615.211.3
1.70 V89.868.260.746.036.926.314.711.0
1.75 V86.265.058.244.435.225.514.410.8
1.80 V82.561.955.042.633.824.414.010.6
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time5 min8 min10 min15 min20 min30 min60 min1.5H
1.60 V17313512494.976.452.630.323.1
1.67 V16813211992.074.552.130.222.5
1.70 V16612811689.372.551.629.321.9
1.75 V16112311286.669.350.128.721.6
1.80 V15511910783.466.448.028.021.2
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
TemperatureCapacity (20 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.