AGM  /  HR Series  /  Datasheet

ATB AGM HR12-300

HR Series · High-Rate AGM VRLA
ATB-AGM-HR12-300

High-rate AGM.
Power for UPS bursts.

A 12 V 78 Ah high-rate AGM VRLA battery for short-duration, high-current UPS discharge. Sealed, maintenance-free and non-spillable, with M6 bolt terminals.

ATB-AGM-HR12-300
12 V
Nominal voltage
300 W
Per cell · 15 min to 1.67 V
780 A
Max discharge (5 s)
24.0 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

M6 bolt terminals

Threaded M6 terminals for secure bolted cable connections in UPS and standby systems.

High-rate discharge

Optimised for short, high-current discharge in UPS systems.

Standard footprint

260 × 168 × 216 mm case.

SPECIFICATIONS

MECHANICAL

Length260 mm ±2.5
Width168 mm ±1.5
Container height211 mm ±2.5
Overall height216 mm ±2.5
Approx. weight24.0 kg ±5%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeM6 bolt terminal

ELECTRICAL

Nominal voltage12 V
ChemistryAGM VRLA (sealed)
Nominal capacity300 W/cell (15 min to 1.67 V/cell, 25°C) · 78 Ah (C20) · 52 Ah (C1)
Float voltage @ 25°C13.5 – 13.8 V
Equalizing voltage @ 25°C14.4 – 15.0 V
Max charge current23.40 A
Max discharge current780.00 A (5 s)
Internal resistance (charged)≈ 6.0 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-HR12-300 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time5 min8 min10 min15 min20 min30 min60 min90 min
1.60 V24421419816613599.557.641.3
1.67 V22219618315512794.255.039.7
1.70 V21218917615012391.953.938.9
1.75 V19617616514211788.052.037.7
1.80 V17916315413411284.350.136.4
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time5 min8 min10 min15 min20 min30 min60 min90 min
1.60 V449398372316260193108.278.2
1.67 V418374351300248185104.175.6
1.70 V404363342293242182102.474.6
1.75 V37934332528023317699.672.5
1.80 V35332230626822417096.670.6
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
TemperatureCapacity (20 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.