AGM  /  GP Series  /  Datasheet

ATB AGM GP6-1.3

GP Series · General Purpose AGM VRLA
ATB-AGM-GP6-1.3

Compact sealed AGM.
Dependable backup power.

A 6 V 1.3 Ah general-purpose AGM VRLA battery for security and alarm systems, UPS, emergency lighting and portable equipment. Valve-regulated oxygen-recombination construction with corrosion-resistant alloy grids, a high-strength AGM separator and high-purity active materials gives low self-discharge and long service life, in a sealed, maintenance-free, non-spillable package with faston tab terminals.

ATB-AGM-GP6-1.3
6 V
Nominal voltage
1.3 Ah
C20 capacity @ 25°C
19.5 A
Max discharge (5 s)
0.29 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

Faston tab terminals

4.75 mm T1 faston tabs for quick, tool-light connection in OEM assemblies, alarms and equipment.

Long service life

Corrosion-resistant alloy grids and a high-strength AGM separator with high-purity active materials give low self-discharge and long float life.

Compact & versatile

97 × 24 × 58 mm case for panels, alarms and portable equipment.

SPECIFICATIONS

MECHANICAL

Length97 mm ±1.5
Width24 mm ±1.0
Container height52 mm ±1.5
Overall height58 mm ±1.5
Approx. weight0.29 kg ±5%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeFaston T1 (4.75 mm tab)

ELECTRICAL

Nominal voltage6 V
ChemistryAGM VRLA (sealed)
Capacity, 20 hr (C20)1.3 Ah
Capacity, 10 hr (C10)1.2 Ah
Capacity, 5 hr (C5)1.1 Ah
Rating basisto 1.75 V/cell @ 25°C
Float voltage @ 25°C6.75 – 6.90 V
Equalizing voltage @ 25°C7.20 – 7.50 V
Max charge current0.39 A
Max discharge current19.5 A (5 s)
Internal resistance (charged)≈ 70 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-GP6-1.3 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time5 min15 min30 min1 h3 h5 h10 h20 h
1.60 V4.512.191.280.7900.3420.2300.1250.067
1.67 V4.142.101.240.7700.3360.2270.1240.066
1.70 V3.972.061.220.7700.3320.2250.1230.066
1.75 V3.701.991.190.7500.3290.2210.1210.065
1.80 V3.441.911.170.7400.3230.2190.1200.064
1.85 V3.161.841.140.7300.3190.2150.1180.064
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time5 min15 min30 min1 h3 h5 h10 h20 h
1.60 V8.304.102.411.520.6670.4510.2490.134
1.67 V7.693.962.361.490.6560.4440.2450.132
1.70 V7.413.882.321.480.6500.4400.2430.131
1.75 V6.953.772.281.460.6430.4360.2400.130
1.80 V6.463.662.251.440.6350.4310.2380.129
1.85 V6.003.552.191.410.6260.4250.2360.127
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
TemperatureCapacity (20 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.