AGM  /  GP Series  /  Datasheet

ATB AGM GP12-35

GP Series · General Purpose AGM VRLA
ATB-AGM-GP12-35

Sealed AGM power.
Built for standby duty.

A 12 V 35 Ah general-purpose AGM VRLA battery for UPS, telecom, security and emergency lighting systems and energy storage. Valve-regulated oxygen-recombination construction with corrosion-resistant alloy grids, a high-strength AGM separator and high-purity active materials gives low self-discharge and long service life, in a sealed, maintenance-free, non-spillable package with M6 bolt terminals.

ATB-AGM-GP12-35
12 V
Nominal voltage
35 Ah
C20 capacity @ 25°C
330 A
Max discharge (5 s)
10 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

M6 bolt terminals

Threaded M6 terminals for secure bolted cable connections in UPS and standby systems.

Long service life

Corrosion-resistant alloy grids and a high-strength AGM separator with high-purity active materials give low self-discharge and long float life.

Standard footprint

196 × 131 × 168 mm case for battery cabinets, racks and UPS enclosures.

SPECIFICATIONS

MECHANICAL

Length196 mm ±2.0
Width131 mm ±1.5
Container height155 mm ±2.0
Overall height168 mm ±2.0
Approx. weight10 kg ±3%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeM6 bolt terminal

ELECTRICAL

Nominal voltage12 V
ChemistryAGM VRLA (sealed)
Capacity, 20 hr (C20)35 Ah
Capacity, 10 hr (C10)33 Ah
Capacity, 5 hr (C5)29.5 Ah
Rating basisto 1.80 V/cell @ 25°C
Float voltage @ 25°C13.5 – 13.8 V
Equalizing voltage @ 25°C14.4 – 15.0 V
Max charge current9.9 A
Max discharge current330 A (5 s)
Internal resistance (charged)≈ 10.5 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-GP12-35 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time10 min15 min30 min1 h3 h5 h10 h20 h
1.60 V67.058.534.721.19.486.303.451.81
1.67 V64.856.834.220.89.366.243.411.79
1.70 V62.855.133.720.59.306.123.371.77
1.75 V58.951.933.120.09.126.003.341.75
1.80 V54.347.932.419.18.945.903.301.73
1.85 V47.842.329.818.48.225.613.151.67
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time10 min15 min30 min1 h3 h5 h10 h20 h
1.60 V11310463.739.618.112.26.843.58
1.67 V11110263.439.318.112.16.723.55
1.70 V11010162.938.917.911.96.663.50
1.75 V10495.762.238.417.711.86.603.47
1.80 V97.689.661.436.717.411.66.543.44
1.85 V87.280.256.935.616.111.06.243.33
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
TemperatureCapacity (20 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.