AGM  /  GP Series  /  Datasheet

ATB AGM GP12-200

GP Series · General Purpose AGM VRLA
ATB-AGM-GP12-200

Sealed AGM power.
Built for standby duty.

A 12 V 206 Ah general-purpose AGM VRLA battery for UPS, telecom, security and emergency lighting systems and energy storage. Valve-regulated oxygen-recombination construction with corrosion-resistant alloy grids, a high-strength AGM separator and high-purity active materials gives low self-discharge and long service life, in a sealed, maintenance-free, non-spillable package with M8 bolt terminals.

ATB-AGM-GP12-200
12 V
Nominal voltage
206 Ah
C20 capacity @ 25°C
1200 A
Max discharge (5 s)
58 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

M8 bolt terminals

Threaded M8 terminals for secure bolted cable connections in UPS, telecom and storage systems.

Long service life

Corrosion-resistant alloy grids and a high-strength AGM separator with high-purity active materials give low self-discharge and long float life.

Standard footprint

522 × 240 × 223 mm case for battery cabinets, racks and UPS enclosures.

SPECIFICATIONS

MECHANICAL

Length522 mm ±2.5
Width240 mm ±2.0
Container height218 mm ±2.5
Overall height223 mm ±2.5
Approx. weight58 kg ±3%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeM8 bolt terminal

ELECTRICAL

Nominal voltage12 V
ChemistryAGM VRLA (sealed)
Capacity, 20 hr (C20)206 Ah
Capacity, 10 hr (C10)200 Ah
Capacity, 5 hr (C5)175 Ah
Rating basisto 1.80 V/cell @ 25°C
Float voltage @ 25°C13.5 – 13.8 V
Equalizing voltage @ 25°C14.4 – 15.0 V
Max charge current60 A
Max discharge current1200 A (5 s)
Internal resistance (charged)≈ 3.2 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-GP12-200 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time30 min45 min1 h3 h5 h8 h10 h20 h
1.60 V20614912554.537.625.020.810.8
1.67 V20314712354.137.024.620.610.6
1.70 V20014512153.536.224.220.410.5
1.75 V19614211952.635.623.820.210.4
1.80 V19213711351.635.023.820.010.3
1.85 V17712910947.533.422.618.79.92
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time30 min45 min1 h3 h5 h8 h10 h20 h
1.60 V37827723510472.649.040.421.2
1.67 V37627523310471.848.440.021.0
1.70 V37427323110370.647.839.620.8
1.75 V36926922810269.847.239.220.6
1.80 V36526221810068.847.039.020.4
1.85 V33824921292.765.644.837.219.8
EFFECT OF TEMPERATURE ON CAPACITY (10 HR)
TemperatureCapacity (10 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.