Compact sealed AGM.
Dependable backup power.
A 12 V 12 Ah general-purpose AGM VRLA battery for security and alarm systems, UPS, emergency lighting and portable equipment. Valve-regulated oxygen-recombination construction with corrosion-resistant alloy grids, a high-strength AGM separator and high-purity active materials gives low self-discharge and long service life, in a sealed, maintenance-free, non-spillable package with faston tab terminals.

Sealed AGM VRLA
Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.
Faston tab terminals
6.35 mm T2 faston tabs for quick, tool-light connection in UPS, alarm and OEM equipment.
Long service life
Corrosion-resistant alloy grids and a high-strength AGM separator with high-purity active materials give low self-discharge and long float life.
Compact & versatile
151 × 98.5 × 101 mm case for panels, alarms and portable equipment.
MECHANICAL
| Length | 151 mm ±1.5 |
| Width | 98.5 mm ±1.5 |
| Container height | 95 mm ±1.5 |
| Overall height | 101 mm ±2.0 |
| Approx. weight | 3.45 kg ±5% |
| Container material | ABS, UL94-HB (UL94-V0 optional) |
| Terminal type | Faston T2 (6.35 mm tab) |
ELECTRICAL
| Nominal voltage | 12 V |
| Chemistry | AGM VRLA (sealed) |
| Capacity, 20 hr (C20) | 12 Ah |
| Capacity, 10 hr (C10) | 11.4 Ah |
| Capacity, 5 hr (C5) | 10.4 Ah |
| Rating basis | to 1.75 V/cell @ 25°C |
| Float voltage @ 25°C | 13.5 – 13.8 V |
| Equalizing voltage @ 25°C | 14.4 – 15.0 V |
| Max charge current | 3.6 A |
| Max discharge current | 180 A (5 s) |
| Internal resistance (charged) | ≈ 16.0 mΩ |
| Operating temp. (dis / chg) | −15°C~50°C / −15°C~40°C |
| Storage temp. | −15°C~40°C |

ATB-AGM-GP12-12 — technical data
| F.V (V/cell) / Time | 5 min | 15 min | 30 min | 1 h | 3 h | 5 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 52.4 | 25.5 | 14.1 | 7.97 | 3.20 | 2.15 | 1.17 | 0.616 |
| 1.67 V | 49.3 | 24.7 | 13.7 | 7.80 | 3.13 | 2.11 | 1.16 | 0.609 |
| 1.70 V | 47.7 | 24.0 | 13.5 | 7.68 | 3.11 | 2.09 | 1.15 | 0.605 |
| 1.75 V | 45.6 | 23.2 | 13.2 | 7.55 | 3.07 | 2.07 | 1.14 | 0.600 |
| 1.80 V | 43.2 | 22.5 | 12.8 | 7.39 | 3.01 | 2.04 | 1.12 | 0.593 |
| 1.85 V | 40.3 | 21.5 | 12.5 | 7.21 | 2.96 | 2.01 | 1.11 | 0.587 |
| F.V (V/cell) / Time | 5 min | 15 min | 30 min | 1 h | 3 h | 5 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 93.5 | 47.5 | 26.7 | 15.2 | 6.21 | 4.20 | 2.32 | 1.23 |
| 1.67 V | 89.9 | 46.1 | 26.1 | 14.9 | 6.12 | 4.15 | 2.29 | 1.22 |
| 1.70 V | 87.6 | 45.2 | 25.7 | 14.8 | 6.07 | 4.12 | 2.28 | 1.21 |
| 1.75 V | 84.4 | 44.0 | 25.2 | 14.5 | 5.99 | 4.07 | 2.25 | 1.20 |
| 1.80 V | 81.1 | 42.8 | 24.7 | 14.4 | 5.91 | 4.03 | 2.23 | 1.19 |
| 1.85 V | 76.1 | 41.1 | 24.1 | 14.0 | 5.83 | 3.97 | 2.20 | 1.17 |
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
| Temperature | Capacity (20 HR) |
|---|---|
| 40 °C | 102% |
| 25 °C | 100% |
| 0 °C | 85% |
| −15 °C | 65% |
SELF-DISCHARGE CHARACTERISTICS
| Storage time | Remaining capacity |
|---|---|
| 3 months | 91% |
| 6 months | 82% |
| 12 months | 64% |
Discharge Characteristics

Charging Characteristics

Capacity Retention (Self-Discharge)

Float Service Life

STANDARDS & QUALITY
AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.
Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.