AGM  /  FT Series  /  Datasheet

ATB AGM FT12-175

FT Series · Front Terminal AGM VRLA
ATB-AGM-FT12-175

Front-terminal AGM.
Made for telecom racks.

A 12 V 183 Ah front-terminal AGM VRLA battery for telecom and UPS racks, with high energy density and a robust grid design. Sealed, maintenance-free and non-spillable, with M8 bolt terminals.

ATB-AGM-FT12-175
12 V
Nominal voltage
183 Ah
C20 capacity @ 25°C
1360 A
Max discharge (5 s)
53.5 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

M8 bolt terminals

Threaded M8 terminals for secure bolted cable connections in UPS, telecom and storage systems.

Front-access design

Both terminals on the front face for installation and inspection in racks.

Standard footprint

561 × 125 × 316 mm case.

SPECIFICATIONS

MECHANICAL

Length561 mm ±2.5
Width125 mm ±2.0
Container height316 mm ±2.5
Overall height316 mm ±2.5
Approx. weight53.5 kg ±3%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeM8 bolt terminal

ELECTRICAL

Nominal voltage12 V
ChemistryAGM VRLA (sealed)
Capacity, 20 hr (C20)183 Ah
Capacity, 10 hr (C10)170 Ah
Capacity, 5 hr (C5)155.5 Ah
Rating basisto 1.80 V/cell @ 25°C
Float voltage @ 25°C13.5 – 13.8 V
Equalizing voltage @ 25°C14.4 – 15.0 V
Max charge current51 A
Max discharge current1360 A (5 s)
Internal resistance (charged)≈ 4.0 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-FT12-175 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time30 min45 min1 h3 h5 h8 h10 h20 h
1.60 V17512710646.333.421.317.79.57
1.67 V17312510546.032.920.917.59.45
1.70 V17012310345.532.220.617.39.34
1.75 V16712110144.731.720.217.29.25
1.80 V16411696.443.931.120.217.09.16
1.85 V15011093.040.429.719.215.98.82
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time30 min45 min1 h3 h5 h8 h10 h20 h
1.60 V32123520088.764.641.734.318.9
1.67 V32023419888.463.941.134.018.7
1.70 V31823219787.962.840.633.718.5
1.75 V31422919486.662.140.133.318.3
1.80 V31022218585.361.240.033.218.1
1.85 V28721118078.858.438.131.617.6
EFFECT OF TEMPERATURE ON CAPACITY (10 HR)
TemperatureCapacity (10 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.