AGM  /  Deep Cycle  /  Datasheet

ATB AGM DC6-400

DC Series · Deep Cycle AGM VRLA
ATB-AGM-DC6-400

Deep-cycle AGM.
Built for repeated cycling.

A 6 V 400 Ah deep-cycle AGM VRLA battery engineered for repeated discharge to 50% DoD or deeper. A rugged thick-plate grid design and high active-material density give high cycle life in motive power, solar and renewable-energy storage and marine use. Sealed, maintenance-free and non-spillable, with DT terminals.

ATB-AGM-DC6-400
6 V
Nominal voltage
400 Ah
C20 capacity @ 25°C
2400 A
Max discharge (5 s)
56 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

DT terminals

DT terminals for secure bolted cable connections.

Deep-cycle design

Thick plates and high active-material density for repeated deep discharge.

Standard footprint

296 × 178 × 426 mm case.

SPECIFICATIONS

MECHANICAL

Length296 mm ±2
Width178 mm ±1.5
Container height405 mm ±2
Overall height426 mm ±3
Approx. weight56 kg ±3%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeDT terminal

ELECTRICAL

Nominal voltage6 V
ChemistryAGM VRLA (sealed)
Capacity, 20 hr (C20)400 Ah
Capacity, 10 hr (C10)373 Ah
Capacity, 5 hr (C5)340 Ah
Rating basisto 1.75 V/cell @ 25°C
Float voltage @ 25°C6.75 – 6.90 V
Equalizing voltage @ 25°C7.20 – 7.50 V
Max charge current120 A
Max discharge current2400 A (5 s)
Internal resistance (charged)≈ 1.8 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-DC6-400 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time30 min45 min1 h3 h5 h8 h10 h20 h
1.60 V39329224410570.947.438.620.6
1.67 V38128523810369.746.638.020.3
1.70 V37528123610269.146.237.720.2
1.75 V36727623210168.045.737.320.0
1.80 V35927022899.467.445.136.819.8
1.85 V35026522398.366.344.636.419.6
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time30 min45 min1 h3 h5 h8 h10 h20 h
1.60 V74355446720513993.776.641.3
1.67 V72654345820213792.075.440.7
1.70 V71453745420013591.474.940.4
1.75 V70353144819813490.373.740.0
1.80 V69152344219513389.773.139.6
1.85 V67451543519313188.672.639.2
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
TemperatureCapacity (20 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.