AGM  /  Deep Cycle  /  Datasheet

ATB AGM DC12-55

DC Series · Deep Cycle AGM VRLA
ATB-AGM-DC12-55

Deep-cycle AGM.
Built for repeated cycling.

A 12 V 55 Ah deep-cycle AGM VRLA battery engineered for repeated discharge to 50% DoD or deeper. A rugged thick-plate grid design and high active-material density give high cycle life in motive power, solar and renewable-energy storage and marine use. Sealed, maintenance-free and non-spillable, with M6 bolt terminals.

ATB-AGM-DC12-55
12 V
Nominal voltage
55 Ah
C20 capacity @ 25°C
550 A
Max discharge (5 s)
16.7 kg
Approx. weight

Sealed AGM VRLA

Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.

M6 bolt terminals

Threaded M6 terminals for secure bolted cable connections in UPS and standby systems.

Deep-cycle design

Thick plates and high active-material density for repeated deep discharge.

Standard footprint

230 × 138 × 215 mm case.

SPECIFICATIONS

MECHANICAL

Length230 mm ±2.5
Width138 mm ±1.5
Container height210 mm ±2.5
Overall height215 mm ±2.5
Approx. weight16.7 kg ±3%
Container materialABS, UL94-HB (UL94-V0 optional)
Terminal typeM6 bolt terminal

ELECTRICAL

Nominal voltage12 V
ChemistryAGM VRLA (sealed)
Capacity, 20 hr (C20)55 Ah
Capacity, 10 hr (C10)51.3 Ah
Capacity, 5 hr (C5)46.8 Ah
Rating basisto 1.75 V/cell @ 25°C
Float voltage @ 25°C13.5 – 13.8 V
Equalizing voltage @ 25°C14.4 – 15.0 V
Max charge current16.5 A
Max discharge current550 A (5 s)
Internal resistance (charged)≈ 8.0 mΩ
Operating temp. (dis / chg)−15°C~50°C / −15°C~40°C
Storage temp.−15°C~40°C
CONTAINER DRAWING — DIMENSIONS IN MM
Container drawing
Technical Specification

ATB-AGM-DC12-55 — technical data

CONSTANT CURRENT DISCHARGE @ 25°C · UNIT: A
F.V (V/cell) / Time10 min15 min30 min1 h3 h5 h10 h20 h
1.60 V12392.754.033.614.59.745.302.84
1.67 V11688.852.432.814.29.595.232.80
1.70 V11387.251.632.514.19.515.192.78
1.75 V10884.150.531.913.99.355.132.75
1.80 V10480.949.331.413.79.275.062.73
1.85 V98.277.848.130.713.59.115.012.70
CONSTANT POWER DISCHARGE @ 25°C · UNIT: W/CELL
F.V (V/cell) / Time10 min15 min30 min1 h3 h5 h10 h20 h
1.60 V22917410264.228.219.110.55.67
1.67 V21816799.863.027.718.810.45.59
1.70 V21416498.262.527.518.610.35.56
1.75 V20516096.661.627.218.510.15.50
1.80 V19615595.160.726.918.210.15.45
1.85 V18815092.759.826.518.010.05.39
EFFECT OF TEMPERATURE ON CAPACITY (20 HR)
TemperatureCapacity (20 HR)
40 °C102%
25 °C100%
0 °C85%
−15 °C65%
SELF-DISCHARGE CHARACTERISTICS
Storage timeRemaining capacity
3 months91%
6 months82%
12 months64%
CHARACTERISTIC CURVES
Discharge Characteristics
TERMINAL VOLTAGE (V/CELL) vs DISCHARGE TIME · 25°C / 20°C
Discharge Characteristics
Charging Characteristics
0.1 CA · 2.25 V/CELL @ 25°C
Charging Characteristics
Capacity Retention (Self-Discharge)
CAPACITY RETENTION RATIO vs STORAGE TIME
Capacity Retention (Self-Discharge)
Float Service Life
FLOAT LIFE vs BATTERY TEMPERATURE · 2.25 V/CELL
Float Service Life

STANDARDS & QUALITY

AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.

Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.