Deep-cycle AGM.
Built for repeated cycling.
A 12 V 40 Ah deep-cycle AGM VRLA battery engineered for repeated discharge to 50% DoD or deeper. A rugged thick-plate grid design and high active-material density give high cycle life in motive power, solar and renewable-energy storage and marine use. Sealed, maintenance-free and non-spillable, with M6 bolt terminals.

Sealed AGM VRLA
Valve-regulated oxygen-recombination design. Maintenance-free and non-spillable: no electrolyte topping and no acid handling.
M6 bolt terminals
Threaded M6 terminals for secure bolted cable connections in UPS and standby systems.
Deep-cycle design
Thick plates and high active-material density for repeated deep discharge.
Standard footprint
197 × 168 × 170 mm case.
MECHANICAL
| Length | 197 mm ±2.0 |
| Width | 168 mm ±1.5 |
| Container height | 170 mm ±2.0 |
| Overall height | 170 mm ±2.0 |
| Approx. weight | 13 kg ±3% |
| Container material | ABS, UL94-HB (UL94-V0 optional) |
| Terminal type | M6 bolt terminal |
ELECTRICAL
| Nominal voltage | 12 V |
| Chemistry | AGM VRLA (sealed) |
| Capacity, 20 hr (C20) | 40 Ah |
| Capacity, 10 hr (C10) | 37.3 Ah |
| Capacity, 5 hr (C5) | 34 Ah |
| Rating basis | to 1.75 V/cell @ 25°C |
| Float voltage @ 25°C | 13.5 – 13.8 V |
| Equalizing voltage @ 25°C | 14.4 – 15.0 V |
| Max charge current | 12 A |
| Max discharge current | 400 A (5 s) |
| Internal resistance (charged) | ≈ 9.0 mΩ |
| Operating temp. (dis / chg) | −15°C~50°C / −15°C~40°C |
| Storage temp. | −15°C~40°C |

ATB-AGM-DC12-40 — technical data
| F.V (V/cell) / Time | 10 min | 15 min | 30 min | 1 h | 3 h | 5 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 89.7 | 67.4 | 39.3 | 24.4 | 10.5 | 7.09 | 3.86 | 2.06 |
| 1.67 V | 84.6 | 64.6 | 38.1 | 23.8 | 10.3 | 6.97 | 3.80 | 2.03 |
| 1.70 V | 82.3 | 63.4 | 37.5 | 23.6 | 10.2 | 6.91 | 3.77 | 2.02 |
| 1.75 V | 78.9 | 61.1 | 36.7 | 23.2 | 10.1 | 6.80 | 3.73 | 2.00 |
| 1.80 V | 75.4 | 58.9 | 35.9 | 22.8 | 9.94 | 6.74 | 3.68 | 1.98 |
| 1.85 V | 71.4 | 56.6 | 35.0 | 22.3 | 9.83 | 6.63 | 3.64 | 1.96 |
| F.V (V/cell) / Time | 10 min | 15 min | 30 min | 1 h | 3 h | 5 h | 10 h | 20 h |
|---|---|---|---|---|---|---|---|---|
| 1.60 V | 167 | 126 | 74.3 | 46.7 | 20.5 | 13.9 | 7.66 | 4.13 |
| 1.67 V | 159 | 122 | 72.6 | 45.8 | 20.2 | 13.7 | 7.54 | 4.07 |
| 1.70 V | 155 | 119 | 71.4 | 45.4 | 20.0 | 13.5 | 7.49 | 4.04 |
| 1.75 V | 149 | 116 | 70.3 | 44.8 | 19.8 | 13.4 | 7.37 | 4.00 |
| 1.80 V | 143 | 113 | 69.1 | 44.2 | 19.5 | 13.3 | 7.31 | 3.96 |
| 1.85 V | 137 | 109 | 67.4 | 43.5 | 19.3 | 13.1 | 7.26 | 3.92 |
EFFECT OF TEMPERATURE ON CAPACITY (10 HR)
| Temperature | Capacity (10 HR) |
|---|---|
| 40 °C | 102% |
| 25 °C | 100% |
| 0 °C | 85% |
| −15 °C | 65% |
SELF-DISCHARGE CHARACTERISTICS
| Storage time | Remaining capacity |
|---|---|
| 3 months | 91% |
| 6 months | 82% |
| 12 months | 64% |
Discharge Characteristics

Charging Characteristics

Capacity Retention (Self-Discharge)

Float Service Life

STANDARDS & QUALITY
AGM VRLA batteries produced by an ATB-approved manufacturing partner whose VRLA batteries are UL-recognized components under UL 1989, in facilities certified to ISO 9001, ISO 14001 and ISO 45001. Sealed, non-spillable VRLA construction.
Values are subject to variation of ±5% under normal manufacturing processes. Technical specifications are subject to change without prior notice. Curves represent typical performance for the AGM VRLA cell platform at the stated reference conditions. This product is engineered, specified and branded by ATB Power. E&OE. © ATB Power.