When mains fails, a UPS battery has minutes to deliver. HR series tunes plate design for high-current discharge over 5 to 30 minutes — the duty UPS specifies and where rate-of-fall matters.
Thinner plates with higher specific surface area. Optimised for short, hard discharges instead of slow cycle duty.
Standard heights match cabinet U-spaces. M5 and M6 terminals depending on capacity.
Maintenance-free. Low gassing under float. Multi-orientation install for tight rack environments.
Constant-power discharge tested per IEC 60896-22. Watts-per-cell published for 5, 10, 15 and 30 minute durations.
HR series rates capacity in watts at the cell level — the metric UPS designers actually use. Plate count, separator porosity and grid alloy all favour high-current discharge over slow cycling. AGM separator and calcium-tin grids minimise water loss.
AGM blocks tuned for short, high-current UPS discharge. Watts-per-cell rated. 12V from 37 to 520 W/cell at 15 minutes.
| Model | Voltage | C20 (Ah) | L × W × H (mm) | Weight | Terminal |
|---|---|---|---|---|---|
| ATB AGM HR12-37 | 12V | 9Ah | 151 × 65 × 94 | 2.57 kg | F1 |
| ATB AGM HR12-92 | 12V | 22Ah | 181 × 77 × 167 | 6.3 kg | M5 |
| ATB AGM HR12-120 | 12V | 30Ah | 165 × 126 × 175 | 9 kg | M5 |
| ATB AGM HR12-150 | 12V | 34Ah | 196 × 131 × 155 | 11 kg | M6 |
| ATB AGM HR12-250 | 12V | 57Ah | 230 × 138 × 210 | 18 kg | M6 |
| ATB AGM HR12-300 | 12V | 78Ah | 260 × 168 × 211 | 24 kg | M6 |
| ATB AGM HR12-420 | 12V | 118Ah | 332 × 175 × 215 | 32 kg | M6 |
| ATB AGM HR12-520 | 12V | 143Ah | 341 × 173 × 282 | 42.5 kg | M6 |
HR12-37
HR12-150
HR12-300
HR12-520Representative sizes shown. Full HR Series range and datasheets at atbpower.com.
HR series ships with watt-per-cell discharge tables for 1, 5, 10, 15, 30 and 60 minute durations. UPS designers can size strings against constant-power discharge curves available on request through atbpower.com.