Front-terminal access lets installers wire and service batteries from a single face. Sized for 19-inch racks, telecom cabinets and outdoor enclosures. 55 to 200 Ah at C20.
Connections sit on the front face. Installers wire from one side. Servicing without lifting blocks out.
Heights and widths sized for 19-inch and ETSI cabinets. Same form factor across the range.
Wide temperature operating range. Sealed VRLA tolerates outdoor enclosures within thermal management limits.
Calcium-tin grid alloy with thicker positive plates. 10 to 12 year float life at 25 °C in stationary duty.
FT series uses a long, low form factor with M8 front-terminal posts. AGM separator and recombination chemistry tolerate cycling and float duty. Design verified to IEC 60896-21 and IEC 60896-22 for stationary VRLA.
M8 front-terminal AGM blocks for cabinet and rack installs. Same height across the range simplifies bus-bar layout. 12V from 55 to 200 Ah.
| Model | Voltage | C20 (Ah) | L × W × H (mm) | Weight | Terminal |
|---|---|---|---|---|---|
| ATB AGM FT12-55 | 12V | 57.8Ah | 277 × 106 × 223 | 18 kg | M6 |
| ATB AGM FT12-70 | 12V | 76Ah | 390 × 105 × 255 | 25.6 kg | M8 |
| ATB AGM FT12-75 | 12V | 82Ah | 562 × 114 × 188 | 27 kg | M8 |
| ATB AGM FT12-100 | 12V | 108.2Ah | 507 × 105 × 223 | 30 kg | M8 |
| ATB AGM FT12-150 | 12V | 161.2Ah | 551 × 110 × 288 | 46 kg | M8 |
| ATB AGM FT12-180 | 12V | 193.4Ah | 561 × 120 × 316 | 55.5 kg | M8 |
| ATB AGM FT12-200 | 12V | 214Ah | 561 × 125 × 316 | 58 kg | M8 |
FT12-55
FT12-75
FT12-100
FT12-180Representative sizes shown. Full FT Series range and datasheets at atbpower.com.
FT series ships with M8 stainless front-terminal posts, copper bus-bar kits available, and a ten-year stationary warranty under standard float operating conditions. Datasheets, certificates of conformity and test reports available via atbpower.com.