Stationary 2V AGM cells string into 24V, 48V and 110V banks for telecom, utility and industrial backup. Long design life. Individual cell replacement keeps total system lifetime longer than block-only solutions.
Tubular and flat-plate 2V designs deliver 15 to 20 year stationary life under controlled float.
Replace individual cells without retiring the entire bank. Lower total cost over a 20-year horizon.
-48V telecom plant and utility-grid backup. Sized for cabinet and floor-mount rack installs.
Sealed VRLA AGM with calcium-tin grids. Low water loss, low gassing under float, recombination chemistry.
2V AGM cells use thick tubular or flat-plate positive grids with high-purity lead-calcium-tin alloy. Float life of 15-20 years at 25°C is typical. Float voltage 2.23-2.27V per cell. Boost charge 2.40V max. Cell-by-cell test data provided for matched strings.
2V AGM cells for utility-scale stationary banks. Floor-mount rack installs. Individual cell replacement extends total bank lifetime beyond 20 years in float duty.
| Model | Voltage | C20 (Ah) | L × W × H (mm) | Weight | Terminal |
|---|---|---|---|---|---|
| ATB AGM 2V-100 | 2V | 108.8Ah | 171 × 72 × 204 | 5.6 kg | M8 |
| ATB AGM 2V-200 | 2V | 206Ah | 171 × 106 × 330 | 13 kg | M8 |
| ATB AGM 2V-300 | 2V | 318Ah | 171 × 151 × 330 | 18 kg | M8 |
| ATB AGM 2V-500 | 2V | 530Ah | 241 × 171 × 330 | 28 kg | M8 |
| ATB AGM 2V-1000 | 2V | 1060Ah | 471 × 171 × 330 | 57.5 kg | M8 |
| ATB AGM 2V-1500 | 2V | 2120Ah | 476 × 337 × 330 | 111 kg | M8 |
| ATB AGM 2V-2000 | 2V | 2660Ah | 476 × 337 × 330 | 122 kg | M8 |
| ATB AGM 2V-3000 | 2V | 3180Ah | 696 × 340 × 330 | 166 kg | M8 |
2V-100
2V-500
2V-1000
2V-3000Representative sizes shown. Full 2V Series range and datasheets at atbpower.com.
2V series ships with matched cell test data, factory commissioning guides and recommended monitoring intervals. Supplied with cell-mount rack hardware on request. Datasheets via atbpower.com.