AGM — Absorbed Glass Mat
Lead-Acid VRLALead-acid VRLA in its most versatile form. Seven series built around the chemistry and plate design for each duty: thin plates for cranking, thicker plates for cycling, lead-carbon plates for partial-state-of-charge operation. Every model listed below is live in the ATB range.
SSL Series — Start-Stop AGM
AGM for start-stop vehicles with idle-off, regenerative braking and frequent engine restarts. Lead-carbon plate technology delivers three times the cycle life of standard SLI, with strong charge acceptance and reliable cold cranking across repeated micro-hybrid cycles.
European LN1 to LN6 fitment. Tested to EN 50342 with over 400 endurance cycles and 8,000 micro-hybrid cycles.
| Model | Voltage | Group Size | C20 (Ah) | CCA (A, EN) | RC (min, 25A) | Dimensions (mm) | Weight |
|---|---|---|---|---|---|---|---|
| ATB AGM SSL1 | 12V | 140R/H4 | 50Ah | 570 A | 80 min | 207 × 175 × 190 | 15.5 kg |
| ATB AGM SSL2 | 12V | 47/H5 | 60Ah | 660 A | 100 min | 242 × 175 × 190 | 18.5 kg |
| ATB AGM SSL3 | 12V | 48/H6 | 70Ah | 720 A | 120 min | 278 × 175 × 190 | 21 kg |
| ATB AGM SSL4 | 12V | 94R/H7 | 80Ah | 800 A | 140 min | 315 × 175 × 190 | 24 kg |
| ATB AGM SSL5 | 12V | 49/H8 | 92Ah | 850 A | 160 min | 353 × 175 × 190 | 26.5 kg |
| ATB AGM SSL6 | 12V | 95R/H9 | 105Ah | 950 A | 190 min | 394 × 175 × 190 | 30 kg |
SSL-1
SSL-2
SSL-3
SSL-4
SSL-5Every SSL shares the same AGM lead-carbon plate technology. Match the size to your vehicle and get consistent start-stop performance across the lineup.
GP Series — General Purpose VRLA
Sealed AGM across the most common backup loads. From small solar home systems and security panels at 4.5 Ah to telecom cabinets, UPS strings and emergency lighting at 200 Ah.
Sealed VRLA. Maintenance-free. Multi-orientation install. Very low self-discharge and stable float voltage.
4.5 to 200 Ah across 6V and 12V. Design life five years under 20 Ah, ten years at 20 Ah and above at 25 °C in float duty. For front-terminal rack access, specify the FT series.
| Model | Voltage | C20 (Ah) | C10 (Ah) | C5 (Ah) | Dimensions (mm) | Weight | Terminal |
|---|---|---|---|---|---|---|---|
| ATB AGM GP12-1.2 | 12V | 1.3Ah | 1.15Ah | 1.1Ah | 97 × 43 × 51.5 | 0.55 kg | F1 |
| ATB AGM GP12-2.3 | 12V | 2.3Ah | 2Ah | 1.95Ah | 97 × 43 × 51 | 0.55 kg | F1 |
| ATB AGM GP12-5 | 12V | 5Ah | 4.7Ah | 4.3Ah | 90 × 70 × 100 | 1.56 kg | F1 |
| ATB AGM GP12-7 | 12V | 7Ah | 6.6Ah | 6Ah | 151 × 65 × 94 | 2.05 kg | F1 |
| ATB AGM GP12-9 | 12V | 9Ah | 8.5Ah | 7.7Ah | 151 × 65 × 94 | 2.43 kg | F2 |
| ATB AGM GP12-12 | 12V | 12Ah | 11.4Ah | 10.2Ah | 151 × 98.5 × 95 | 3.45 kg | F2 |
| ATB AGM GP12-18 | 12V | 18Ah | 16.2Ah | 14.5Ah | 151 × 98 × 95 | 3.45 kg | M5 |
| ATB AGM GP12-26 | 12V | 26Ah | 24Ah | 22.5Ah | 175 × 165 × 127 | 7.35 kg | M5 |
| ATB AGM GP12-35 | 12V | 35Ah | 33Ah | 28.5Ah | 196 × 131 × 155 | 10 kg | M6 |
| ATB AGM GP12-40 | 12V | 42Ah | 40Ah | 34Ah | 197 × 166 × 170 | 11.7 kg | M6 |
| ATB AGM GP12-55 | 12V | 58Ah | 55Ah | 48Ah | 230 × 138 × 210 | 16.7 kg | M6 |
| ATB AGM GP12-70 | 12V | 68Ah | 65Ah | 55Ah | 348 × 167 × 177 | 20 kg | M6 |
| ATB AGM GP12-100 | 12V | 77Ah | 75Ah | 67.5Ah | 260 × 168 × 211 | 21.7 kg | M6 |
| ATB AGM GP12-120 | 12V | 120Ah | 111Ah | 96Ah | 332 × 175 × 215 | 32 kg | M8 |
| ATB AGM GP12-150 | 12V | 156Ah | 150Ah | 134Ah | 482 × 170 × 240 | 44.5 kg | M8 |
| ATB AGM GP12-200 | 12V | 210Ah | 200Ah | 186Ah | 522 × 240 × 218 | 58 kg | M8 |
| ATB AGM GP12-200 | 12V | 270Ah | 260Ah | 225Ah | 522 × 240 × 218 | 58 kg | M8 |
GP12-7
GP12-18
GP12-55
GP12-100
GP12-200DC Series — Deep-Cycle AGM
Deep-cycle AGM for daily charge and discharge in off-grid solar, residential inverter banks, marine house banks and shift-cycle motive equipment. Plates and grid alloy specified for cycling duty rather than cranking.
Thick positive plates, high-tin grid alloy and high-density active paste tolerate 80% depth-of-discharge across thousands of cycles. Sealed VRLA, gas-recombinant, multi-orientation install. No topping up, no off-gassing.
Eighteen models across 6V, 8V and 12V from 35 to 260 Ah. Strong charge recovery from deep cycles. Low self-discharge for long storage between shifts. Operating range −20 to 55 °C.
| Model | Voltage | C20 (Ah) | C5 (Ah) | C3 (Ah) | Dimensions (mm) | Weight | Terminal |
|---|---|---|---|---|---|---|---|
| ATB AGM DC6-224 | 6V | 224Ah | 179Ah | 161Ah | 260 × 180 × 248 | 30.5 kg | M8 |
| ATB AGM DC6-250 | 6V | 250Ah | 200Ah | 180Ah | 260 × 182 × 269 | 34.4 kg | M8 |
| ATB AGM DC6-335 | 6V | 335Ah | 268Ah | 241Ah | 296 × 178 × 345 | 47 kg | DT |
| ATB AGM DC6-400 | 6V | 400Ah | 320Ah | 288Ah | 296 × 178 × 405 | 56 kg | DT |
| ATB AGM DC8-200 | 8V | 200Ah | 160Ah | 144Ah | 260 × 180 × 280 | 37.4 kg | M8 |
| ATB AGM DC12-35 | 12V | 35Ah | 28Ah | 25Ah | 195 × 131 × 155 | 9.9 kg | M6 |
| ATB AGM DC12-55 | 12V | 55Ah | 44Ah | 40Ah | 229 × 136 × 210 | 16.4 kg | M6 |
| ATB AGM DC12-85 | 12V | 85Ah | 68Ah | 61Ah | 260 × 168 × 211 | 25 kg | M8 |
| ATB AGM DC12-105 | 12V | 105Ah | 84Ah | 76Ah | 306 × 169 × 216 | 28 kg | M8 |
| ATB AGM DC12-210 | 12V | 210Ah | 168Ah | 151Ah | 522 × 240 × 219 | 58 kg | M8 |
| ATB AGM DC12-260 | 12V | 260Ah | 208Ah | 187Ah | 520 × 268 × 220 | 73.5 kg | LT |
DC12-35
DC12-85
DC12-105
DC12-210
DC12-260Need to match a specific floor scrubber, scissor lift, MEWP or golf car to a DC Series battery? Use the equipment selector on the Motive application page →
HR Series — High-Rate VRLA
High-rate sealed lead-acid AGM sized for short-duration, high-current UPS discharge. Purpose-built for large data centers, UPS/EPS and emergency power systems.
Performance rated in watts per cell at the 15-minute discharge rate to 1.67 volts per cell end-of-discharge. Pick the model by required power per string, not by amp-hour capacity.
Specialized grid plate design and alloy with low internal resistance. Thin-plate construction delivers high power density for runtime windows between 5 and 30 minutes.
| Model | Voltage | W/cell @15min | C20 (Ah) | C5 (Ah) | Dimensions (mm) | Weight | Terminal |
|---|---|---|---|---|---|---|---|
| ATB AGM HR12-37 | 12V | 37W | 9Ah | 7.7Ah | 151 × 65 × 94 | 2.57 kg | F1 |
| ATB AGM HR12-92 | 12V | 92W | 21.5Ah | 18.5Ah | 181 × 77 × 167 | 6.3 kg | M5 |
| ATB AGM HR12-120 | 12V | 120W | 30Ah | 26Ah | 165 × 125 × 175 | 9 kg | M5 |
| ATB AGM HR12-150 | 12V | 150W | 34Ah | 30Ah | 195 × 130 × 155 | 11 kg | M6 |
| ATB AGM HR12-250 | 12V | 250W | 57Ah | 53Ah | 229 × 138 × 210 | 18 kg | M6 |
| ATB AGM HR12-300 | 12V | 300W | 78Ah | 67Ah | 260 × 169 × 211 | 24 kg | M6 |
| ATB AGM HR12-350 | 12V | 350W | 94Ah | 80Ah | 306 × 169 × 211 | 28.5 kg | M6 |
| ATB AGM HR12-420 | 12V | 420W | 118Ah | 100Ah | 332 × 175 × 215 | 32 kg | M6 |
| ATB AGM HR12-520 | 12V | 520W | 143Ah | 134Ah | 341 × 173 × 282 | 42.5 kg | M6 |
HR12-37
HR12-92
HR12-150
HR12-300
HR12-520FT Series — Front Terminal
Front-terminal AGM for telecom cabinets, UPS and power network installs where front access matters. Ten year design life at 25 °C in float service.
Lead-calcium grid alloy with AGM separator. Front-terminal layout simplifies rack maintenance: install, connect and inspect from the cabinet face.
Sized for 19-inch and 23-inch telecom shelves and indoor UPS cabinets. 55 Ah to 200 Ah at the C10 rate, 12V.
| Model | Voltage | C10 (Ah) | C20 (Ah) | C5 (Ah) | Dimensions (mm) | Weight | Terminal |
|---|---|---|---|---|---|---|---|
| ATB AGM FT12-55 | 12V | 55Ah | 60Ah | 50.8Ah | 277 × 106 × 223 | 16 kg | M6 front |
| ATB AGM FT12-75 | 12V | 75Ah | 82Ah | 69.3Ah | 562 × 114 × 188 | 27 kg | M8 front |
| ATB AGM FT12-80 | 12V | 80Ah | 87Ah | 73.9Ah | 390 × 105 × 255 | 29.3 kg | M8 front |
| ATB AGM FT12-100 | 12V | 100Ah | 109Ah | 92.4Ah | 507 × 109 × 223 | 32 kg | M8 front |
| ATB AGM FT12-125 | 12V | 125Ah | 136Ah | 115.5Ah | 550 × 105 × 315 | 44.6 kg | M8 front |
| ATB AGM FT12-150 | 12V | 150Ah | 163Ah | 138.6Ah | 569 × 110 × 290 | 47.5 kg | M8 front |
| ATB AGM FT12-170 | 12V | 170Ah | 185Ah | 157.1Ah | 561 × 125 × 316 | 52.4 kg | M8 front |
| ATB AGM FT12-180 | 12V | 180Ah | 196Ah | 166.3Ah | 561 × 125 × 316 | 55.5 kg | M8 front |
| ATB AGM FT12-200 | 12V | 200Ah | 217Ah | 184.8Ah | 561 × 125 × 316 | 61.7 kg | M8 front |
FT12-55
FT12-75
FT12-100
FT12-180LC Series — Lead-Carbon AGM
Lead-carbon AGM for solar self-consumption and partial-state-of-charge duty — the operating window where standard AGM loses capacity within twelve to eighteen months.
Lead-carbon negative plates reduce sulfation under partial-state-of-charge operation, the duty common to solar self-consumption installs. Lower internal resistance and stronger charge acceptance than standard AGM under the same conditions. Over 2,200 cycles at 20% depth-of-discharge at 25 °C per manufacturer testing.
Sixteen models across 6V and 12V from 12 to 400 Ah at C10. Sealed VRLA, maintenance-free, multi-orientation install. Built for hybrid inverter systems, off-grid and hot-climate standby.
| Model | Voltage | C10 (Ah) | C20 (Ah) | C5 (Ah) | Dimensions (mm) | Weight | Terminal |
|---|---|---|---|---|---|---|---|
| ATB LC12-200 | 12V | 200Ah | 215Ah | 182.8Ah | 520 × 268 × 220 | 65 kg | M8 |
| ATB LC12-230 | 12V | 230Ah | 245Ah | 208.3Ah | 520 × 268 × 220 | 72 kg | M8 |
LC12-200
LC12-2302V Series — High-Density VRLA Cells
2V VRLA cells for large UPS banks, utility standby, telecom central office, rail and power-plant DC systems. Capacities from 100 Ah to 3,000 Ah per cell.
Thick-plate design, low-weight electrolyte, sealed post construction. Low self-discharge for long storage between installs. Design life 10 years at 25 °C in float service.
| Model | Voltage | C20 (Ah) | C10 (Ah) | C100 (Ah) | Dimensions (mm) | Weight | Terminal |
|---|---|---|---|---|---|---|---|
| ATB AGM 2V-100 | 2V | 110Ah | 100Ah | 121.77Ah | 171 × 72 × 204 | 5.6 kg | M8 |
| ATB AGM 2V-200 | 2V | 200Ah | 184Ah | 220Ah | 170 × 106 × 332 | 12.5 kg | M8 |
| ATB AGM 2V-300 | 2V | 300Ah | 276Ah | 330Ah | 172 × 151 × 319 | 18 kg | M8 |
| ATB AGM 2V-600 | 2V | 600Ah | 552Ah | 660Ah | 285 × 171 × 330 | 36.5 kg | M8 |
| ATB AGM 2V-1500 | 2V | 2150Ah | 2000Ah | 2380.05Ah | 476 × 337 × 330 | 111 kg | M8 |
2V-100
2V-500
2V-1000
2V-1500
2V-3000All specifications nominal at 25°C. Weights and dimensions typical. Blank fields are pending vendor confirmation. LC capacities published at the C10 rate. Full datasheets and product drawings on request.