Guide · Lead-Acid
Lead-Acid Guide

How to Charge VRLA Batteries Correctly (and Make Them Last)

Most lead-acid batteries die from poor charging, not age. Get the voltages, temperature and timing right and you will get the full life.

ATB Power · Battery Solutions  ·  6 min read

Charging is the single biggest factor in VRLA battery life. The goal is to return the charge fully and promptly, without overcharging. Use a constant-voltage, current-limited charger set to the right profile.

Constant currentConstant voltageCharge currentBattery voltageCharge time
Constant-current / constant-voltage (CC/CV) charging: hold the current until the battery reaches the charge voltage, then hold the voltage while current tapers.

Target voltages (per 12 V, 25 C)

ModeAGMGEL
Cyclic / boost14.4 to 14.7 V14.1 to 14.4 V
Float / standby13.5 to 13.8 V13.6 to 13.8 V
Max charge currentup to 0.30 Cup to 0.20 C

For 6 V batteries use half these voltages; for 2 V cells use the per-cell figures (2.40 to 2.45 VPC cyclic, 2.25 to 2.30 VPC float). Always defer to the model datasheet.

Compensate for temperature

Adjust about minus 4 mV per cell per degree C away from 25 C (around minus 24 mV/C for a 12 V battery). Raise voltage when cold, lower it when hot. Many smart chargers do this automatically.

Habits that extend life

Quick check

A rested, fully charged 12 V VRLA reads about 12.8 to 12.9 V. Below 12.4 V it needs charging before use or storage.